Deterioration of stator winding insulation continues to be one of the predominant causes of large motor and generator failures. Over the past several years, practical methods have been developed for measuring the partial discharge activity in the high voltage insulation of stator windings, since partial discharges are a symptom of most of the insulation failure mechanisms in motors and generators rated 4 kV or more. The turbine generator analyzer (TGA) test has now been specifically developed to enable industrial plant staff to reliably perform a partial discharge test on operating motors and turbine generators. This paper presents several case studies of the use of these new partial discharge test technologies on rotating machines. Test results show that machines with deteriorated windings have a partial discharge activity at least 30 times higher than good windings. The availability of these test methods enables plant staff to economically and reliably plan stator winding maintenance, avoid unexpected failures and often extend the time between major maintenance outages.
机译:定子绕组绝缘性能的恶化仍然是导致大型电动机和发电机故障的主要原因之一。在过去的几年中,已经开发出了用于测量定子绕组的高压绝缘中的局部放电活动的实用方法,因为局部放电是额定值为4 kV或更高的电动机和发电机中大多数绝缘失效机制的症状。现已专门开发了涡轮发电机分析仪(TGA)测试,以使工厂的工作人员能够可靠地对运行中的电动机和涡轮发电机进行局部放电测试。本文介绍了在旋转机器上使用这些新的局部放电测试技术的几个案例研究。测试结果表明,绕组损坏的电机的局部放电活动至少是良好绕组的30倍。这些测试方法的可用性使工厂员工能够经济,可靠地计划定子绕组的维护,避免意外故障,并经常延长两次重大维护中断之间的时间。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号