Electrical and Thermal Analyses of Parallel Single-Conductor Cable Installations

机译:平行单导体电缆安装的电气和热分析

获取原文
获取原文并翻译 | 示例
           

摘要

The unequal current distribution in parallel single-conductor cable installations can lead to an excessive temperature rise. This paper presents a cable model and a procedure of coupled electrical and thermal analyses for the evaluation of the current, loss, and temperature in the cables of concern. The cable model and analytical method were tested experimentally on a cable system in the laboratory. The procedure was applied to evaluate the current rating and the temperature rise in a particular single-conductor installation. It is concluded that the parallel cable installation without proper cable rephrasing derates the cables significantly. The third-order harmonic current can cause a significant reduction of the current rating if its distortion is over 30%.
机译:并联单芯电缆安装中的电流分布不均会导致温度过度升高。本文介绍了电缆模型以及耦合的电气和热分析程序,以评估所关注电缆的电流,损耗和温度。电缆模型和分析方法在实验室的电缆系统上进行了实验测试。该程序用于评估特定单导体安装中的额定电流和温度升高。可以得出结论,没有适当改写电缆的并行电缆安装会严重降低电缆的性能。如果三次谐波电流的畸变超过30%,则可能导致额定电流的显着降低。