As a result of new requirements in the National Fire Protection Association (NFPA) 70E standard, many facilities are performing arc-flash hazard analyses to better understand how to protect personnel from the possibility of being injured in an arc-flash incident. In many cases in the petrochemical industry, it is unsafe or not practical to shut down electrical equipment to do work. This paper explores practicable options that a facility has to reduce incident energy levels in existing low-voltage systems where the arc-flash hazard analysis results in unacceptably high levels. It also explores a case study in the Gulf of Mexico, where an offshore oil production platform was able to cost effectively reduce incident energy levels from approximately 170 to under 15 $hbox{calories/cm}^{2}$ by implementing a zone selective interlocking system into their low-voltage switchgear. The selection process logic involving equipment, personnel considerations, and commissioning are all addressed.
机译:由于美国国家消防协会(NFPA)70E标准提出了新要求,因此许多设施都在进行弧闪危害分析,以更好地了解如何保护人员免受弧闪事故伤害的可能性。在石化行业中,在许多情况下,关闭电气设备进行工作是不安全的或不切实际的。本文探讨了一种可行的选择,即设施必须降低现有低压系统中的入射能量水平,在现有低压系统中,闪弧危害分析的结果将导致不可接受的高水平。它还探索了墨西哥湾的一个案例研究,在该案例中,海上石油生产平台通过实施区域选择性管理,能够有效地将入射能级从170美元降低到15美元hbox {calories / cm} ^ {2} $以下联锁系统进入其低压开关柜。涉及设备,人员考虑和调试的选择过程逻辑都得到解决。