摘要

While performing a routine unlock and energization on a medium-voltage motor starter, the job scope changed to involve troubleshooting the equipment to attempt to find the cause of apparent linkage binding. As the electrical worker began reassembling the starter and inserting the large double-barrel fuses, he inadvertently pushed the racking assembly in, which caused the shutters to open and the stabs to contact the energized 2400-V bus. The worker's bare right hand was on the fuse ferule and the electrical current entered his body through his hand and exited through his left knee. This paper describes the incident in detail and discusses what was learned from the event.
机译:在中压电动机启动器上执行常规解锁和通电时,工作范围已更改为涉及对设备进行故障排除,以试图找出明显的联动装置绑定的原因。电气工人开始重新组装起动器并插入大型双桶式熔断器时,他无意中将机架组件推入,导致百叶窗打开,并且插口接触通电的2400-V总线。工人裸露的右手在保险丝上,电流通过他的手进入他的身体,并通过他的左膝盖流出。本文详细描述了该事件,并讨论了从该事件中学到的东西。