首页> 外文期刊>Indoor and built environment >Can Clean-Room Particle Counters be Used as an Infection Control Tool in Hospital Operating Theatres?
【24h】

Can Clean-Room Particle Counters be Used as an Infection Control Tool in Hospital Operating Theatres?

机译:洁净室颗粒计数器可以用作医院手术室中的感染控制工具吗?

获取原文
获取原文并翻译 | 示例
           

摘要

Current UK guidelines for the commissioning of hospital operating theatres rely on air-flow checks, identification of "short-circuits" and measurement of airborne microbiological levels under design conditions when the theatre is idle. There is currently no guideline for infection control teams to investigate theatres when an increased infection risk is suspected. This study aims to examine the use of clean-room particle counters as an infection control tool by monitoring particle profiles in air as a surrogate for infectious particles. Particle counters (three- and six-channel) were used to simultaneously measure particle concentrations at the theatre inlet area, two outlets and bed area, under design and working conditions. A significant increase in particles of all size ranges (0.3 to > 10 μm diameter) was observed when people were introduced. Particle distribution was uneven, with response to environmental changes different at the two outlets. Removal efficiency varied from 52-100%, due to the introduction of particles to the theatre. Within the bed area, significantly different concentrations were measured under design and working conditions; corresponding microbiological samples indicated an associated increase in airborne bacteria. We concluded that particle counters can be used in some aspects of infection control, although more studies are required to fully explore their potential.
机译:英国目前有关医院手术室调试的指导原则取决于在手术室闲置时在设计条件下的气流检查,“短路”的识别以及空气中微生物水平的测量。当怀疑感染风险增加时,目前没有指导方针供感染控制小组调查剧院。这项研究旨在通过监测空气中的微粒概况(作为传染性微粒的替代品)来检查无尘室微粒计数器作为感染控制工具的用途。在设计和工作条件下,使用粒子计数器(三通道和六通道)同时测量剧院入口区域,两个出口和床区域的颗粒浓度。当人们被介绍时,观察到所有大小范围(直径从0.3到> 10μm)的颗粒都显着增加。颗粒分布不均匀,两个出口对环境变化的响应不同。由于将颗粒引入剧院,去除效率从52-100%不等。在病床区域内,在设计和工作条件下测得的浓度存在明显差异。相应的微生物样本表明,空气传播细菌的增加。我们得出的结论是,尽管需要进行更多的研究以充分挖掘其潜力,但粒子计数器仍可以用于感染控制的某些方面。

著录项

  • 来源
    《Indoor and built environment》 |2012年第3期|p.381-391|共11页
  • 作者单位

    Healthy Infrastructure Research Centre, Department of Civil, Environmental and Geomatic Engineering, University College London, Gower Street, London, WC1E 6BT;

    Healthy Infrastructure Research Centre, Department of Civil, Environmental and Geomatic Engineering, University College London, Gower Street, London, WC1E 6BT;

    Microbiology, Virology and Infection Prevention and Control Department,Great Ormond Street Hospital for Children NHS Trust, Great Ormond Street, London, WC1N 3JH;

    Microbiology, Virology and Infection Prevention and Control Department,Great Ormond Street Hospital for Children NHS Trust, Great Ormond Street, London, WC1N 3JH;

    Healthy Infrastructure Research Centre, Department of Civil, Environmental and Geomatic Engineering, University College London, Gower Street, London, WC1E 6BT;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    particles; ventilation; infection control; healthcare; pathogens; air;