A classical lead-lag power system stabilizer is used for demonstration in this paper. Initially single first-order phase compensation block is considered. The stabilizer parameters are selected in such a manner to damp the rotor oscillations. The problem of selecting the stabilizer parameters is converted to a simple optimization problem with an eigen value based objective function and it is proposed to employ simulated annealing and improved simulated annealing for solving optimization problem. The objective function allows the selection of the stabilizer parameters to optimally place the closed-loop eigen values in the left hand side of the complex s-plane. The effectiveness of the stabilizer tuned using the best technique, in enhancing the stability of power system. Stability is confirmed through eigen value analysis and simulation results and suitable heuristic technique will be selected for the best performance of the system.
机译:本文使用经典的超前滞后电力系统稳定器进行演示。最初考虑单个一阶相位补偿块。选择稳定器参数的方式应能阻尼转子的振动。将选择稳定器参数的问题转换为具有基于特征值的目标函数的简单优化问题,并提出采用模拟退火和改进的模拟退火来解决优化问题。目标函数允许选择稳定器参数,以将闭环特征值最佳地放置在复杂s平面的左侧。使用最佳技术调整的稳定器的有效性,可以提高电力系统的稳定性。通过特征值分析和仿真结果可以确定稳定性,并且将选择合适的启发式技术来获得最佳系统性能。