Effect of Lightning Protective Devices Attached to Pole Transformers on Reduction of Overvoltage on Distribution Lines

机译:固定在杆式变压器上的防雷装置对配电线路上过电压降低的影响

获取原文
获取原文并翻译 | 示例
           

摘要

Class-10 A solid-core insulators (BIL 90 kV) have been used instead of class-6A pin insulators (BIL 60 kV) in order to improve the insulation level of distribution lines. However, lightning protective devices attached to pole transformers may have the effect of reducing the overvoltages on phase conductors. We have investigated the lightning protection effect of devices attached to pole transformers by experiment and analysis using the EMTP (Electro-Magnetic Transients Program). The sparkover rate changes from 2.0-3.3% to 5.5-9.9% and increases 2.4-2.8 times when the line insulator of the phase conductors is changed from class-10 A to class-6 A. It is thought that the insulation level of the line insulator can be reduced depending upon the local particularities, such as number of installed transformers, frequency of direct lightning stroke to the distribution line, and so on although the overall fault rate may increase to some extent.
机译:为了提高配电线路的绝缘水平,已使用10 A类实心绝缘子(BIL 90 kV)代替6A类Pin绝缘子(BIL 60 kV)。但是,连接到极变压器的防雷装置可能会减少相导体上的过电压。我们已经使用EMTP(电磁暂态程序)通过实验和分析研究了连接到极变压器的设备的防雷效果。当相导体的线路绝缘子从10 A级更改为6 A级时,跳火率从2.0-3.3%更改为5.5-9.9%,并增加2.4-2.8倍。据认为,绝缘等级尽管总故障率可能会有所提高,但可以根据局部特性(例如已安装的变压器的数量,直接雷击到配电线路的频率)来减少线路绝缘子。