首页> 外文期刊>電気学会論文誌 B:電力·エネルギー部門誌 >配電用柱上変圧器の雷過電圧応答: 変圧器容量への依存性
【24h】

配電用柱上変圧器の雷過電圧応答: 変圧器容量への依存性

机译:配电杆变压器的雷电过电压响应:取决于变压器容量

获取原文

摘要

配電線上の柱上変圧器は最も雷による被害を受けやすいrn機器であり,雷過電圧に対する変圧器の挙動を解析するrnための様々な等価回路が提案され,シミュレーションに用rnいられている。%A pole-mounted transformer on a power distribution line is vulnerable to lightning overvoltages, and is one of the most frequently damaged instruments in Japan. Therefore, the response of transformers to the overvoltage draws great concern. By incorporating the modeling for the secondary windings proposed by Mr. Honda et al., the authors develop equivalent circuits of distribution transformers of 10kVA, 20kVA and 30kVA rated capacity based on modal analysis of measured admittance whereby one can evaluate its response to overvoltages on a low-voltage line as well as on a medium-voltage line. The validity of calculated results obtained by using the developed circuits is demonstrated by comparison with experimental results. The response of transformers made by the same manufacturer to the lightning impulse voltage waveforms is influenced by the rated capacity, and the phase and the degree of such influence is demonstrated.
机译:配电线路上的极变压器是最容易被雷击损坏的设备,已经提出了各种等效电路来分析变压器抵抗雷电过电压的行为,并将其用于仿真。 %配电线路上的杆式变压器易受雷击过电压的影响,是日本损坏最频繁的仪器之一,在那里,变压器对过电压的响应引起了极大的关注。由Honda等人提出,作者基于对测得的导纳的模态分析,开发了额定容量为10kVA,20kVA和30kVA的配电变压器的等效电路,一个人评估了对低压线路以及低压线路对过电压的响应。通过与实验结果的比较,证明了使用所开发的电路获得的计算结果的有效性。同一制造商制造的变压器对雷电冲击电压波形的响应受额定容量和相位的影响。并说明这种影响的程度。