Calculating the Transient Recovery Voltage Associated With Clearing Transformer Determined Faults by Means of Frequency Response Analysis

机译:通过频率响应分析计算与清除变压器确定的故障相关的暂态恢复电压

获取原文
获取原文并翻译 | 示例

摘要

The transient recovery voltage (TRV) associated with power-transformer terminal faults is essential for correctly applying circuit breakers. Because presently used methods only allow for roughly estimating an equivalent single TRV ringing frequency, more accurate but inexpensive methods are needed. The novel method presented in this paper employs frequency response analysis (FRA) for measuring the transformer's complex short circuit impedance Z{sub}x. From that, the frequency spectrum of the TRV is approximated by the ratio of Z{sub}x over the frequency square. Inverse fast Fourier transformation finally leads to the time domain signal. Comparing measured TRV signals from several field tests with the calculated ones prove this simple but effective method. Even multimode oscillations that cannot be reproduced by rough estimating tools are covered. It is concluded that the presented method provides a valuable tool for extracting inherent TRV parameters, either from routinely performed FRA measurements or from lightning impulse tests without significant additional costs.
机译:与电源变压器端子故障相关的瞬态恢复电压(TRV)对于正确应用断路器至关重要。由于当前使用的方法仅允许粗略估计等效的单个TRV振铃频率,因此需要更准确但便宜的方法。本文介绍的新颖方法采用频率响应分析(FRA)来测量变压器的复短路阻抗Z {sub} x。由此可见,TRV的频谱近似为Z {sub} x在频率平方上的比率。快速傅立叶逆变换最终导致时域信号。将来自多个现场测试的测得的TRV信号与计算得出的TRV信号进行比较,证明了这种简单而有效的方法。甚至涵盖了无法通过粗略估计工具重现的多模振荡。结论是,所提出的方法提供了一种有价值的工具,可以从常规的FRA测量或雷电冲击测试中提取固有的TRV参数,而无需花费大量的额外费用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号