This paper describes a performance evaluation of the Gonen geothermal district heating system (GGDHS) in Balikesir, Turkey, based on energy and exergy analyses. The exergy destructions in the overall GGDHS are quantified and illustrated using energy and exergy flow diagrams for a reference temperature of 6℃. The results indicate that the exergy destructions in the system occur primarily as a result of losses in the pumps, heat exchangers, and pipelines, as well as losses associated with cooled geothermal waters injected back into the reservoir. These losses amount to 14.81%, 7.11%, 1.06%, and 12.96% of the total exergy input to the GGDHS, respectively. Both energy and exergy efficiencies of the overall GGDHS were investigated to analyze and improve system performance. The efficiencies were determined to be 45.91% and 64.06%, respectively.
机译:本文基于能源和火用分析,描述了土耳其巴厘克西尔Gonen地热集中供热系统(GGDHS)的性能评估。在参考温度为6℃的情况下,使用能量和火用流程图定量和说明了整个GGDHS中的火用破坏。结果表明,系统中的火用破坏主要是由于泵,热交换器和管道的损失以及与注入水库的冷却地热水有关的损失所致。这些损失分别占向GGDHS输入的总火用的14.81%,7.11%,1.06%和12.96%。研究了整个GGDHS的能量和火用效率,以分析和改善系统性能。效率分别确定为45.91%和64.06%。