首页> 外文期刊>Generation, Transmission & Distribution, IET >Wavelet-based index to discriminate between minor inter-turn short-circuit and resistive asymmetrical faults in stator windings of doubly fed induction generators: a simulation study
【24h】

Wavelet-based index to discriminate between minor inter-turn short-circuit and resistive asymmetrical faults in stator windings of doubly fed induction generators: a simulation study

机译:基于小波的指数来区分双馈感应发电机定子绕组中的较小匝间短路和电阻性不对称故障:模拟研究

获取原文
获取原文并翻译 | 示例
       

摘要

This study investigates two common types of stator winding faults in doubly fed induction generators (DFIGs) including inter-turn short-circuit fault (ITSCF) and winding resistive asymmetrical fault (WRAF), and compares them with the operation of DFIGs underpower grid voltage unbalance conditions. A complete magnetic equivalent circuit model has been used to model ITSCF and WRAF in the stator windings of DFIG. The aim of this investigation is to discriminate between these types of faults using the rotor-reference-voltage signals inside the rotor-side-converter control system. A new fault diagnostic index (FDI) is proposed based on normalised energy evaluation of the given signal using the discrete wavelet transform. The accuracy of the proposed FDI has been evaluated by simulation of DFIG performances with Matlab/Simulink software under low number of stator shorted turns conditions, different severities of winding resistive asymmetrical faults, various levels of grid voltage unbalance, various rotor speeds, and various output active powers. Analysis of the simulation results confirms that the proposed FDI can accurately discriminate between ITSCF even with minor shorted turns, WRAF or unbalanced voltages except for the cases with minor asymmetry and healthy conditions of stator winding.
机译:本研究调查了双馈感应发电机(DFIG)中两种常见的定子绕组故障,包括匝间短路故障(ITSCF)和绕组电阻非对称故障(WRAF),并将它们与DFIG在电网电压不平衡下的运行进行比较。条件。完整的磁等效电路模型已用于对DFIG定子绕组中的ITSCF和WRAF进行建模。该研究的目的是使用转子侧变流器控制系统内部的转子参考电压信号来区分这些类型的故障。基于给定信号的归一化能量评估,使用离散小波变换,提出了一种新的故障诊断指标(FDI)。通过使用Matlab / Simulink软件对DFIG性能进行仿真,评估了建议的FDI的准确性,该性能在定子短路匝数少,绕组电阻不对称故障严重程度不同,电网电压不平衡水平不同,转子速度不同以及输出量不同的情况下有功功率。对仿真结果的分析证实,除了定子绕组的不对称性较小且运行状况良好的情况外,即使在匝数短,WRAF或电压不平衡的情况下,建议的FDI仍可以准确区分ITSCF。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号