The paper presents an application of video fire analysis (VFA) to a cable tray fire scenario, a scenario of interest to nuclear power plants where cables constitute a substantial part of the combustible load. Five horizontal trays, each 2.4 m long and 0.45 m wide, are positioned with a 0.3 m spacing (in the vertical direction) and set-up against an insulated wall. Each tray contains 49 power PVC cables of 13 mm outer diameter. Ignition is performed with an 80 kW propane burner centrally positioned at 0.2 m below the first (i.e. lowest) tray. Thanks to a flame detection algorithm, the VFA technique allows a reconstruction of the heat release rate (HRR) profile based on the estimated temporal evolution of flame and extinction fronts at the level of each tray. The obtained profile is generally in good agreement with the HRR measurements (from oxygen depletion calorimetry). However, the time to reach the peak HRR is overestimated by approximately 100 s and the peak HRR of 3 MW is underestimated by 17%. These results are nevertheless encouraging because they provide confidence in the flame spread measurements (which are estimated for the case at hand between 2 mm/s and 5 mm/s). Therefore, a systematic application of VFA to real-scale experiments is believed to generate a valuable set of data (e.g. flame spread rates) for the development of simplified modelling.
机译:本文介绍了视频火灾分析(VFA)在电缆桥架火灾场景中的应用,这是核电厂感兴趣的场景,其中电缆构成了可燃负荷的重要部分。五个水平托架(每个长度为2.4 m,宽度为0.45 m)以0.3 m的间隔(垂直方向)放置,并靠着隔热墙设置。每个托盘包含49根外径13 mm的电源PVC电缆。用80 kW丙烷燃烧器点火,该丙烷燃烧器居中位于第一个(即最低)托盘下方0.2 m处。由于使用了火焰检测算法,VFA技术可以根据每个托盘水平的火焰和消光前沿的估计时间演变,重建放热率(HRR)曲线。所获得的曲线通常与HRR测量(从耗氧量热法得出)非常吻合。但是,达到峰值HRR的时间被高估了大约100 s,而3 MW的峰值HRR被低估了17%。但是,这些结果令人鼓舞,因为它们为火焰蔓延测量提供了信心(对于手边的情况估计为2 mm / s至5 mm / s)。因此,据信VFA在实际实验中的系统应用可为开发简化的模型生成有价值的数据集(例如,火焰扩散率)。

著录项

  • 来源
    《Fire Technology》 |2016年第3期|611-621|共11页
  • 作者单位

    Univ Ghent, Dept Flow Heat & Combust Mech, UGent, Sint Pietersnieuwstr 41, B-9000 Ghent, Belgium;

    Univ Ghent, Dept Flow Heat & Combust Mech, UGent, Sint Pietersnieuwstr 41, B-9000 Ghent, Belgium;

    Univ Ghent, ELIS Dept, Multimedia Lab, iMinds, Gaston Crommenlaan 8 Bus 201, B-9050 Ledeberg Ghent, Belgium;

    IRSN, F-13115 St Paul Les Durance, France;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Cable fire spread (CFS); Video fire analysis (VFA);

    机译:电缆火灾蔓延(CFS);视频火灾分析(VFA);
  • 入库时间 2022-08-18 00:11:53

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号