首页> 外文期刊>Fire Safety Journal >Model scale tunnel fire tests with automatic sprinkler
【24h】

Model scale tunnel fire tests with automatic sprinkler

机译:使用自动洒水器进行模型规模的隧道火灾测试

获取原文
获取原文并翻译 | 示例
           

摘要

The study focuses on the performance of an automatic sprinkler system in a model scale tunnel with longitudinal ventilation. A total of 28 tests were carried out in a 1:15 model scale tunnel using an automatic sprinkler system with glass bulbs. The maximum heat release rate, energy content and failure of the automatic sprinkler system were analysed. The results show that high ventilation rates and low water flow rates result in a failure of the automatic sprinkler system in a longitudinal ventilated tunnel fire. The main reason for the failure under the tested water flow rates was the effect of the longitudinal flow on the fire development and the hot gas flow close to the sprinklers. The fire development and the activation heat release rate of the first activated bulb are intimately related to the ventilation velocity. The fire spread to the neighbouring wood crib was investigated and a presentation of tests conducted using a deluge system are given.
机译:该研究的重点是带有纵向通风的模型规模隧道中自动洒水系统的性能。使用带有玻璃灯泡的自动喷水灭火系统,在1:15模型规模的隧道中进行了总共28个测试。分析了自动洒水系统的最大放热率,能量含量和故障。结果表明,高通风率和低水流量会导致自动喷水灭火系统在纵向通风隧道火灾中发生故障。在测试水流量下失败的主要原因是纵向流对火势的影响以及靠近喷头的热气流。点火的发生和第一个启动灯泡的启动散热率与通风速度密切相关。调查了蔓延到相邻木婴儿床的火,并介绍了使用雨淋系统进行的测试。