Failure of a component in BCHP (building cooling, heating and power) system may result in failure of a sub-system or of the whole system. The reliability and availability analysis of BCHP system is helpful to the designer to decide the redundancy in case of equipment failure. This paper presents the redundant design of BCHP system and its operation mode. The SSM (state-space method) combined to the probabilistic analysis of Markov model, is employed to analyze the reliabilities of three forms of energy supply including electricity, heat and cool in BCHP system. The failure rate, the repair rate, the availability and the MTBF (mean time to failure) of the redundant and non-redundant BCHP systems are deduced and analyzed respectively. Then, a numerical case for the reliability analysis of the redundant and non-redundant BCHP systems is compared to the SP (separation production) system. Finally, the calculation results indicate that the reliability of the redundant BCHP system compared to the SP system obviously increases, and the failure rates of the electricity, heat and cool supplies decrease 99.63%, 94.30% and 99.97% respectively.
机译:BCHP(建筑物的制冷,供暖和供电)系统中某个组件的故障可能会导致子系统或整个系统的故障。 BCHP系统的可靠性和可用性分析有助于设计人员确定设备故障时的冗余度。本文介绍了BCHP系统的冗余设计及其运行模式。将状态空间方法与马尔可夫模型的概率分析相结合,用于分析BCHP系统中三种形式的能源供应的可靠性,包括电,热和冷。分别推导和分析了冗余和非冗余BCHP系统的故障率,修复率,可用性和MTBF(平均故障时间)。然后,将用于冗余和非冗余BCHP系统可靠性分析的数值案例与SP(分离生产)系统进行比较。最后,计算结果表明,与SP系统相比,冗余BCHP系统的可靠性明显提高,电力,热力和冷力供应商的故障率分别降低了99.63%,94.30%和99.97%。

著录项

  • 来源
    《Energy》 |2013年第1期|531-540|共10页
  • 作者单位

    School of Energy and Power Engineering, North China Electric Power University, Baoding, Hebei Province 071003, China;

    School of Energy and Power Engineering, North China Electric Power University, Baoding, Hebei Province 071003, China;

    School of Energy and Power Engineering, North China Electric Power University, Baoding, Hebei Province 071003, China;

    School of Energy and Power Engineering, North China Electric Power University, Baoding, Hebei Province 071003, China;

    School of Energy and Power Engineering, North China Electric Power University, Baoding, Hebei Province 071003, China;

    Department of Civil, Environmental and Architectural Engineering, University of Colorado at Boulder, 428 UCB, Boulder, CO 80309-0428, USA;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Building cooling, heating and power (BCHP) system; Reliability; Availability; Redundant design; State space method;

    机译:建筑物的制冷;供暖和发电(BCHP)系统;可靠性;可用性;冗余设计;状态空间法;