首页> 外文期刊>IEEE Transactions on Energy Conversion >Hydrogen leakage due to stress corrosion cracking of stator conductors in 210 MW generator: a case study
【24h】

Hydrogen leakage due to stress corrosion cracking of stator conductors in 210 MW generator: a case study

机译:210 MW发电机定子导体应力腐蚀开裂引起的氢气泄漏:案例研究

获取原文
获取原文并翻译 | 示例

摘要

This paper presents a case study conducted to find out the reasons of rupture/failure at bends of water cooled stator bar in a 210 MW generator. The bars containing hollow and solid subconductors were cleaned to remove the insulation. The failed portions were examined under a scanning electron microscope, optical microscope and the corrosion products by X-ray analysis. The investigation revealed the presence of intergranular brittle cracks, cuprous oxide tarnish film, ammonia, and moisture. All these showed the characteristic features of SCC in copper metal in ammonical solution. The ultimate rupture by SCC of solid and hollow conductors took place in three stages: (1) water leaked from inside the hollow conductor, at the lug braze; (2) the water reacted with the insulation and produced ammonia; and (3) the ammonia caused SCC and led to heavy leakage of water and hydrogen in the generator. Each stage involved in the failure process has been described.
机译:本文介绍了一个案例研究,以找出210 MW发电机水冷定子棒弯曲处破裂/故障的原因。清洁包含空心和实心子导体的条,以去除绝缘层。在扫描电子显微镜,光学显微镜和腐蚀产物下通过X射线分析检查失效部分。调查发现存在晶间脆性裂纹,氧化亚铜锈蚀膜,氨气和水分。所有这些表明铵盐溶液中铜金属中SCC的特征。实心和空心导体的SCC最终破裂发生在三个阶段:(1)水从空心导体内部漏出,在接线片铜焊处; (2)水与保温层反应生成氨气; (3)氨引起SCC,导致发电机中水和氢大量泄漏。已经描述了故障过程中涉及的每个阶段。