首页> 外文期刊>Energy and Buildings >Effect of damper and heat source on wind catcher natural ventilation performance
【24h】

Effect of damper and heat source on wind catcher natural ventilation performance

机译:风门和热源对集热器自然通风性能的影响

获取原文
获取原文并翻译 | 示例
       

摘要

Experimental wind tunnel and smoke visualisation testing and CFD modelling were conducted to investigate the effect of air flow control mechanism and heat source inside rooms on wind catchers/towers performance. For this purpose, a full-scale wind catcher was connected to a test room and positioned centrally in an open boundary wind tunnel. Pressure coefficients (C_p's) around the wind catcher and air flow into the test room were established. The performance of the wind catcher depends greatly on the wind speed and direction. The incorporation of dampers and egg crate grille at ceiling level reduces and regulates the air flow rate with an average pressure loss coefficient of 0.01. The operation of the wind catcher in the presence of heat sources will potentially lower the internal temperatures in line with the external temperatures.
机译:进行了实验性风洞和烟气可视化测试以及CFD建模,以研究室内的气流控制机制和热源对集热器/塔架性能的影响。为此,将一个大型的集气器连接到测试室,并将其放置在开放边界风洞的中央。建立了集尘器周围的压力系数(C_p's)和空气进入测试室的流量。捕风器的性能在很大程度上取决于风速和风向。在天花板水平处并入风门和蛋箱格栅可以减少并调节空气流量,平均压力损失系数为0.01。在存在热源的情况下,捕风器的操作可能会降低内部温度,使其与外部温度一致。

著录项

  • 来源
    《Energy and Buildings》 |2006年第8期|p.939-948|共10页
  • 作者

    Abbas Ali Elmualim;

  • 作者单位

    Innovative Construction Research Centre, School of Construction Management & Engineering, The University of Reading, Reading RG6 6AW, United Kingdom;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类 房屋建筑设备;
  • 关键词

    wind catcher; ventilation; visualisation testing;

    机译:捕风器;通风;可视化测试;