Hospital operating rooms (ORs) require efficient HVAC installations to secure the highly demanding indoor environmental conditions for patients and medical personnel. This paper reviews published standards and guidelines on design, installation, commissioning, operation, and maintenance of HVAC installations in hospital ORs, indoor thermal conditions, and summarizes measured data from short monitoring of indoor thermal conditions along with audit results and main characteristics of 20 ORs in 10 major Hellenic hospitals. Measured indoor temperature ranged from 14 to 29℃, and relative humidity from 13 to 80%. The number of air changes per hour ranged from 3.2 to 58 ACH. The commonly encountered problems include insufficient indoor air exchange, poor control on indoor thermal conditions, bad space ergonomics that influence the ventilation system operation, poor technical installations maintenance and understaffed technical departments. However, there are still opportunities for energy conservation, without sacrificing comfort, and overall quality of patient care or services.
机译:医院手术室(OR)需要高效的HVAC安装,以确保为患者和医务人员提供苛刻的室内环境条件。本文回顾了有关医院手术室,室内热工条件下的HVAC安装的设计,安装,调试,运行和维护的已发布标准和指南,并总结了从对室内热工况的短期监控中得出的测量数据以及审核结果和20个手术室的主要特征。在希腊的10家主要医院中。测得的室内温度范围为14至29℃,相对湿度为13至80%。每小时换气次数为3.2至58 ACH。常见的问题包括室内空气交换不足,对室内热工条件的控制差,影响通风系统运行的不良人机工程学,差劲的技术装置维护和不足的技术部门。然而,在不牺牲舒适度以及患者护理或服务的整体质量的前提下,仍然存在节能的机会。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号