Exergoeconomic Analysis Of The Gonen Geothermal District Heating System For Buildings

机译:建筑物Gonen地热集中供热系统的能效经济分析

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents an application of an exergoeconomic model, through exergy and cost accounting analyses, to the Gonen geothermal district heating system (GDHS) in Balikesir, Turkey for the entire system and its components. This exergoeconomic model is used to reveal the cost formation process and the productive interaction between components. The exergy destructions in the overall Gonen GDHS are quantified and illustrated for a reference temperature of 4 ℃. The results indicate that the exergy destructions in the system occur primarily as a result of losses in the cooled geothermal water injected back into the reservoir, pumps, heat exchangers, and pipelines. Total exergy destruction and reinjection exergy of the cooled geothermal water result in 1010 kW (accounting for 32.49%), 320.3 kW (accounting for 10%) of the total exergy input to the Gonen GDHS, respectively. Both energy and exergy efficiencies of the overall Gonen GDHS are also investigated to analyze the system performance, as these efficiencies are determined to be 42% and 50%, respectively. It is found that an increase of the load condition leads to a decrease in the overall thermal costs, which will result in more cost-effective energy systems for buildings.
机译:本文通过火用和成本核算分析,介绍了一种能干经济模型在土耳其巴厘克西尔的Gonen地热集中供热系统(GDHS)中的整个系统及其组成部分的应用。这种能效经济模型用于揭示成本形成过程和组件之间的生产性相互作用。在参考温度为4℃的情况下,量化并说明了整个Gonen GDHS的火用破坏。结果表明,系统中的火用破坏主要是由于冷却的地热水注入到水库,泵,热交换器和管道中而损失的结果。冷却后的地热水的总火用破坏和再注入火用分别占输入到Gonen GDHS的总火用的1010 kW(占32.49%)和320.3 kW(占10%)。还对整个Gonen GDHS的能量效率和火用效率进行了分析,以分析系统性能,因为确定这些效率分别为42%和50%。发现负载条件的增加导致总热成本的降低,这将导致用于建筑物的更具成本效益的能源系统。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号