首页> 外文期刊>Energy and Buildings >Energy and exergy-based indicators for the energy performance assessment of a hotel building
【24h】

Energy and exergy-based indicators for the energy performance assessment of a hotel building

机译:基于能源和火用指标的酒店建筑能源绩效评估

获取原文
获取原文并翻译 | 示例
           

摘要

Buildings account for 40% of total energy consumption in the European Union. The sector is expanding, which will lead to an increase of its energy consumption, if no additional measures are taken. The Directives 2002/91/EC and 2010/31/EU (recast) on the energy performance of buildings have as objective to reinforce the improvement of the energy performance of buildings, proposing the use of energy performance indicators, based on primary energy use or CO_2 emissions. In this study, the limitations of the actual method are identified and a new indicator, based on exergy, is proposed, aiming to give new insights about the energy use in buildings. As a case study, a hotel building located in Coimbra (Portugal) is analysed using actual energy consumption data derived from a conducted energy audit. Besides primary energy based indicators, two more indicators were used: the primary energy ratio (PER) and exergy efficiency. Results show an estimated overall primary energy consumption of 446kWh/(m~2 year), and 49% and 17%, found as PER and exergy efficiency, respectively. From an individual analysis, the electric equipments were found as the main contributors for the primary energy consumption of the hotel; however, they present the highest exergy efficiency when compared to processes related with space air conditioning.
机译:建筑物占欧盟能源总消耗的40%。如果不采取其他措施,该行业正在扩大,这将导致其能源消耗增加。关于建筑物能源性能的第2002/91 / EC号指令和2010/31 / EU指令(改版)旨在加强建筑物能源性能的改善,并建议基于一次能源的使用或使用能源性能指标CO_2排放量。在这项研究中,确定了实际方法的局限性,并提出了一种基于火用能的新指标,旨在提供有关建筑物能源使用的新见解。作为案例研究,使用从进行的能源审计得出的实际能耗数据分析了位于科英布拉(葡萄牙)的一家旅馆建筑。除了基于主要能源的指标外,还使用了另外两个指标:主要能源比率(PER)和火用效率。结果表明,估计的一次能源总消耗量为446kWh /(m〜2年),PER和火用效率分别为49%和17%。从个人分析来看,电气设备被认为是酒店一次能源消耗的主要贡献者。但是,与空间空调相关的过程相比,它们具有最高的火用效率。

著录项

  • 来源
    《Energy and Buildings》 |2012年第9期|p.181-188|共8页
  • 作者单位

    ADAI-LAETA, Department of Mechanical Engineering, University of Coimbra. Rua Luis Reis Santos. Polo II. 3030-788 Coimbra. Portugal;

    ADAI-LAETA, Department of Mechanical Engineering, University of Coimbra. Rua Luis Reis Santos. Polo II. 3030-788 Coimbra. Portugal;

    ADAI-LAETA, Department of Mechanical Engineering, University of Coimbra. Rua Luis Reis Santos. Polo II. 3030-788 Coimbra. Portugal;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    exergy analysis; energy audits; energy performance of buildings; energy labelling;