This work deals with an experimental and numerical study of an Earth-to-Air Heat Exchanger (EAHX) for air cooling, connected to a residential building located in Marrakech (Morocco) which climate is a hot semi-arid one. The EAHX consists of three parallel PVC pipes of 72 m length each and 15 cm inside diameter, buried at 2.2-3.2 m depth. Each pipe is equipped with a fan, which blows treated air into the building. The experimental study consists of summer monitoring of the EAHX via measurements of air temperature and humidity throughout the exchanger, as well as at its inlet and outlet to the building for two fixed values of the airflow rate. The experimental results show that the EAHX is a good semi passive system for air refreshment, as the recorded blown air temperature into the building is quasi constant at 25 degrees C with air humidity around 40%, even though the outside temperature reaches more than 40 degrees C. Furthermore, the reduction of daily and annual air temperature amplitudes is characterized by an exponential drop as a function of pipe length. The characteristic length is found to be around 20 m and 70m respectively for the daily and annual air temperature amplitudes reduction. Moreover, it is shown that the design guidelines from literature cannot straightforwardly be applied to an EAHX which is subject to meteorological disturbance from the upper surface and/or which is not operated all year round, for which numerical simulation with a validated models remains necessary.
机译:这项工作是对用于空气冷却的地对空热交换器(EAHX)进行的实验和数值研究,该热交换器与位于马拉喀什(摩洛哥)的住宅楼相连,该住宅区是半干旱的热气候。 EAHX由三根平行的PVC管组成,每根管长72 m,内径15 cm,埋在2.2-3.2 m的深度。每个管道都配有风扇,该风扇将处理过的空气吹入建筑物。实验研究包括夏季通过对整个交换器以及建筑物入口和出口处空气温度和湿度的测量来监测EAHX,以获取两个固定的气流速率。实验结果表明,EAHX是一种良好的半被动式空气清新系统,因为记录到建筑物的吹入空气温度在25摄氏度下近似恒定,空气湿度约为40%,即使室外温度超过40摄氏度也是如此。 C.此外,每日和每年的空气温度振幅的降低的特征在于,其作为管道长度的函数呈指数下降。对于每天和每年降低空气温度幅度,特征长度分别约为20 m和70 m。而且,已经表明,文献中的设计指南不能直接应用于受到上表面的气象干扰和/或全年没有运行的EAHX,为此,必须使用经过验证的模型进行数值模拟。

著录项

  • 来源
    《Energy and Buildings》 |2016年第8期|109-121|共13页
  • 作者单位

    Cadi Ayyad Univ, Energy Proc Res Grp LMFE URAC27, Fac Sci Semlalia, Marrakech, Morocco|Cadi Ayyad Univ, EnR2E, Natl Ctr Studies & Res Water & Energy CNEREE, Marrakech, Morocco|Univ La Rochelle, Lab Sci Ingenieur Environm LaSIE, La Rochelle, France;

    Cadi Ayyad Univ, Energy Proc Res Grp LMFE URAC27, Fac Sci Semlalia, Marrakech, Morocco|Cadi Ayyad Univ, EnR2E, Natl Ctr Studies & Res Water & Energy CNEREE, Marrakech, Morocco;

    Univ La Rochelle, Lab Sci Ingenieur Environm LaSIE, La Rochelle, France;

    Univ Geneva, Inst Forel, Sect Sci Terre & Environm, CH-1211 Geneva 4, Switzerland;

    Cadi Ayyad Univ, Energy Proc Res Grp LMFE URAC27, Fac Sci Semlalia, Marrakech, Morocco|Cadi Ayyad Univ, EnR2E, Natl Ctr Studies & Res Water & Energy CNEREE, Marrakech, Morocco;

    Cadi Ayyad Univ, EnR2E, Natl Ctr Studies & Res Water & Energy CNEREE, Marrakech, Morocco;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    TRNSYS; Air cooling; Monitoring; EAHX; Residential building;