Model calibration of a variable refrigerant flow system with a dedicated outdoor air system: A case study

机译:带有专用室外空气系统的可变制冷剂流量系统的模型校准:案例研究

获取原文
获取原文并翻译 | 示例
           

摘要

With increased use of variable refrigerant flow (VRF) systems in the U.S. building sector, interests in capability and rationality of various building energy modeling tools to simulate VRF systems are rising. This paper presents the detailed procedures for model calibration of a VRF system with a dedicated outdoor air system (DOAS) by comparing to detailed measured data from an occupancy emulated small office building. The building energy model is first developed based on as-built drawings, and building and system characteristics available. The whole building energy modeling tool used for the study is U.S. DOE's EnergyPlus version 8.1. The initial model is, then, calibrated with the hourly measured data from the target building and VRF-DOAS system. In a detailed calibration procedures of the VRF-DOAS, the original EnergyPlus source code is modified to enable the modeling of the specific VRF-DOAS installed in the building. After a proper calibration during cooling and heating seasons, the VRF-DOAS model can reasonably predict the performance of the actual VRF-DOAS system based on the criteria from ASHRAE Guideline 14-2014. The calibration results show that hourly CV-RMSE and NMBE would be 15.7% and 3.8%, respectively, which is deemed to be calibrated. The whole-building energy usage after calibration of the VRF-DOAS model is 1.9% (78.8 kWh) lower than that of the measurements during comparison period. (C) 2017 Elsevier B.V. All rights reserved.
机译:随着美国建筑领域对可变制冷剂流量(VRF)系统的使用日益增多,人们对各种建筑能量建模工具来模拟VRF系统的能力和合理性的兴趣日益浓厚。本文通过与模拟占用的小型办公楼的详细测量数据进行比较,介绍了具有专用室外空气系统(DOAS)的VRF系统模型校准的详细程序。首先根据竣工图以及可用的建筑物和系统特性来开发建筑物能源模型。用于研究的整个建筑能源建模工具是美国能源部的EnergyPlus版本8.1。然后,使用来自目标建筑物和VRF-DOAS系统的每小时测量数据对初始模型进行校准。在VRF-DOAS的详细校准过程中,对原始的EnergyPlus源代码进行了修改,以能够对建筑物中安装的特定VRF-DOAS进行建模。经过在制冷和供暖季节的适当校准,VRF-DOAS模型可以根据ASHRAE准则14-2014中的标准合理预测实际VRF-DOAS系统的性能。校准结果表明,每小时CV-RMSE和NMBE分别为15.7%和3.8%,这被认为是已校准。在比较期间,VRF-DOAS模型校准后的整个建筑能耗比测量值低1.9%(78.8 kWh)。 (C)2017 Elsevier B.V.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号