摘要

In the paper load rejection test, provided at a hydro power plant in Sweden, equipped with asynchronous generators, is described and analysed from the electromechanical transient processes and signal distortions points of view. During the test, the shunt capacitors and generator terminal voltages and currents are digitized, recorded and thereafter off-line processed by using Newton Type Algorithm, an efficient non linear estimator. Estimator is utilized for the unknown signal model parameters estimation. The main goal was to investigate the frequency changes and the distortions of the signals processed. Particularly, the frequency changes and the total harmonic distortion factors before and after the instance of load rejection are estimated and discussed. The results given in the paper presents the features of the numerical algorithm used when real data are processed.
机译:在纸张负载抑制试验中,从配备有异步发电机的瑞典的水力发电厂提供,并从机电瞬态过程和信号扭曲视图中描述和分析。在测试期间,通过使用Newton型算法,一种高效的非线性估计器,通过使用Newton型算法进行数字化,记录,然后离线进行分流电容器和发电机端电压和电流。估计器用于未知信号模型参数估计。主要目标是调查频率变化和处理的信号的扭曲。特别地,估计并讨论了负载抑制实例之前和之后的频率变化和总谐波失真因子。本文给出的结果呈现了处理实际数据时使用的数值算法的特征。