For pt.VIII see ibid., vol.7, no.5, p.9 et seq. (1991). The physical aspects of partial discharge (PD) in SF/sub 6/ gas-insulated substations (GIS) are reviewed. The orientation is toward present and developing techniques for evaluating defects in solid and gaseous insulation systems on the basis of PD measurement. Standard evaluation methods provide an indication of PD in GIS, but cannot quantitatively determine the type and size of defect. Statistical analysis of PD activity, together with physical models for the various types of discharge and defects, provides the basis for more advanced interpretation. Measurements of PD activity that do not require an absolute calibration are of greatest utility.
机译:第八节见同上,第7卷,第5期,第9页及以​​下。 (1991)。审查了SF / sub 6 /气体绝缘变电站(GIS)中局部放电(PD)的物理方面。方向是针对目前和正在开发的技术,以基于局部放电测量来评估固体和气体绝缘系统中的缺陷。标准评估方法可以指示GIS中的PD,但不能定量确定缺陷的类型和大小。 PD活动的统计分析,以及各种放电和缺陷的物理模型,为更高级的解释提供了基础。不需要绝对校准的PD活性测量具有最大的实用性。