首页> 外文期刊>IEEE Electrical Insulation Magazine >Thermoluminescence - An Optical Technique for In-situ Measurement of Cross-linking By-products During Degassing of Power Cables
【24h】

Thermoluminescence - An Optical Technique for In-situ Measurement of Cross-linking By-products During Degassing of Power Cables

机译:热致发光-一种在电缆脱气过程中原位测量交联副产物的光学技术

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents a novel optical technique that has been developed to determine the concentration of by-products in chemically cross-linked polymeric materials. Underground power cables, especially of the high-voltage and extra high-voltage class, must be subjected to thermal treatment or conditioning called degassing in order to reduce the concentration of the cross-linking by-products to a negligible level. Degassing causes a reduction and redistribution of the by-products in the insulation of freshly cross-linked cables. It is advantageous to degas cross-linked power cables and reduce the by-products to a low level and stable level so that the electrical tests, performed prior to cable installation, would reveal the true condition of the insulation
机译:本文介绍了一种新颖的光学技术,该技术已被开发出来以确定化学交联的聚合物材料中副产物的浓度。地下电力电缆,特别是高压和超高压类别的地下电缆,必须进行热处理或调理(称为脱气),以将交联副产物的浓度降低至可以忽略的水平。脱气导致新鲜交联电缆绝缘中副产物的减少和重新分布。最好对交联的电缆进行除气,并将副产物降低到较低的水平和稳定的水平,以便在电缆安装之前进行的电气测试可以揭示绝缘的真实状况。