首页> 外文期刊>Electrical Engineers, Proceedings of the Institution of >Measurement of winding temperatures by change of resistance
【24h】

Measurement of winding temperatures by change of resistance

机译:通过电阻变化测量绕组温度

获取原文
获取原文并翻译 | 示例
           

摘要

The normal method used to measure the temperature of the windings of transformers, reactors and other heavy electrical plant is by change of resistance. By means of a simple d.c. test, resistances are measured before and after the heat run. The temperature at shutdown is calculated using the known temperature coefficients of resistance for copper. It is well recognised that inductance may cause errors in these measurements, especially in large transformers. A simple test procedure is presented which enables the presence of inductive errors to be detected. Should they be present, a numerical correction to the measured resistances is readily applied. The principle involved is to place a d.c. millivoltmeter across a winding other than the one under test and note its readings during the period of the cooling curve. By transformer action, the induced e.m.f. may be related to the winding under test and a quantitative correction in ohms derived. The method may be easily applied at any test bench, irrespective as to whether the volt-ammeter, Wheatstone bridge or Kelvin bridge circuits are employed. The only additional equipment required is a vacuum-tube millivoltmeter of common type.
机译:用于测量变压器,电抗器和其他重型电厂的绕组温度的通常方法是通过改变电阻。通过简单的直流电测试中,在热运行之前和之后测量电阻。停机时的温度是使用已知的铜电阻温度系数来计算的。众所周知,电感可能会在这些测量中引起误差,特别是在大型变压器中。提出了一种简单的测试程序,可以检测出感应错误的存在。如果存在电阻,则很容易对测量的电阻进行数值校正。涉及的原则是放置一个直流电。跨过除被测绕组之外的另一绕组的毫伏表,并记录其在冷却曲线期间的读数。通过变压器的作用,感应的e.m.f.可能与被测绕组以及以欧姆为单位的定量校正有关。该方法可以容易地应用于任何测试台,无论是否使用电压-电流表,惠斯通电桥或开尔文电桥电路。唯一需要的附加设备是普通类型的真空管毫伏表。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号