Many of the restrictions for dwelling units can be found in Section 210.11, which deals with the number and sizes of branch circuits for lighting and appliances, including motor-operated appliances. Section 210.11(A)(1) provides the requirements for the minimum number of branch circuits for a dwelling unit. It is based on the total calculated load and requires the load be evenly proportioned among all the branch circuits, based on the dwelling unit's volt-ampere load per square foot. However, the remainder of 210.11 provides more specific requirements for various parts of the dwelling unit. For example, 210.11(C) (1) requires at least two or more 20A branch circuits be provided for all receptacle outlets specified by 210.52(B), such as kitchen, dining and breakfast room circuits (to serve all wall outlets with walls 2 feet or wider and any floor receptacles located within 18 inches of the wall and to have a receptacle outlet within 6 feet horizontally on any wall space).
机译:居住单元的许多限制可以在第210.11节中找到,这涉及用于照明和设备的分支电路的数量和尺寸,包括电动器具。 第210.11节(a)(1)提供了住宅单元的最小分支电路数的要求。 它基于总计算的负载,并且需要在所有分支电路之间均匀地按比例均匀成比例,基于每平方英尺的居住单元的伏安负载。 然而,210.11的其余部分为住宅单元的各个部分提供了更具体的要求。 例如,210.11(c)(1)需要为210.52(b)(如厨房,餐饮和早餐室电路)规定的所有插座插座提供至少两个或更多个20A分支电路(以墙壁2服务 脚或更宽的脚部和任何地板容器,位于18英寸的墙壁内,并且在任何墙上的空间上水平地设有6英尺的插座出口。