This paper describes several system configurations that could lead to very high breaker transient recovery voltage (TRV) and rate of rise of recovery voltage (RRRV) in the presence of phase-shifting transformers, synchronous condensers, and switched capacitor banks. The special considerations involved in determining the most limiting TRV and RRRV are presented. Mitigation measures required for 15 kV and 115 kV breakers that are applied in the above system configurations are also presented. Simulation results presented are part of a design study carried out for the proposed extension to Granite Station in Vermont.
机译:本文介绍了几种系统配置,在存在相移变压器,同步电容器和开关电容器组的情况下,这些配置可能会导致非常高的断路器瞬态恢复电压(TRV)和恢复电压的上升速率(RRRV)。介绍了确定最大TRV和RRRV涉及的特殊注意事项。还介绍了在上述系统配置中应用的15 kV和115 kV断路器所需的缓解措施。提出的模拟结果是对拟议中的佛蒙特州花岗岩站扩建工程进行的设计研究的一部分。