首页> 外文期刊>Electric power systems research >A study on high-voltage substation ground grid integrity measurement
【24h】

A study on high-voltage substation ground grid integrity measurement

机译:高压变电站接地网完整性测量研究

获取原文
获取原文并翻译 | 示例

摘要

The condition of the substation grounding grid is vital for the safety of the people. Inadequate grounding may cause failures in major substation's equipment, as well as in control, metering and telecommunication equipment. Therefore, it is necessary to clearly identify damaged elements on grounding grid. This paper presents an approach to test the integrity of the grounding grid in a general framework of IEEE Std. 81-2012. More precisely, in order to locate damaged grounding riser(s) and/or grounding grid conductor(s), this paper is focused on novel unambiguous criteria for post-processing of raw-data collected from the measurements. In order to avoid the effect of power frequency interference on the measurement, we use DC test current of 100A. The field test is described and discussed in details. The outcome of field test clearly shows the validity and feasibility of the proposed approach. (C) 2015 Elsevier B.V. All rights reserved.
机译:变电站接地网的状况对于人员安全至关重要。接地不充分可能会导致大型变电站的设备以及控制,计量和电信设备出现故障。因此,有必要明确识别接地网上的损坏元件。本文提出了一种在IEEE Std通用框架中测试接地网完整性的方法。 81-2012。更准确地说,为了定位损坏的接地立管和/或接地栅格导体,本文着重于对从测量中收集的原始数据进行后处理的新颖明确标准。为了避免工频干扰对测量的影响,我们使用100A的直流测试电流。详细描述和讨论了现场测试。现场测试的结果清楚地表明了该方法的有效性和可行性。 (C)2015 Elsevier B.V.保留所有权利。