首页> 外文期刊>Electric power systems research >Approximate method to compute the maximum rms current in a distribution feeder due to simultaneous inrush currents in downstream transformers
【24h】

Approximate method to compute the maximum rms current in a distribution feeder due to simultaneous inrush currents in downstream transformers

机译:由于下游变压器同时涌入电流而引起的配电馈线最大均方根电流的近似计算方法

获取原文
获取原文并翻译 | 示例
           

摘要

This article shows an approximate method to compute the maximum rms current in a distribution feeder due to simultaneous inrush currents in downstream transformers. In the first part of the article, a method for the exact calculation of inrush currents in distribution transformers (by solving the differential equations) is tested. This exact model was verified with experimental measurements. Subsequently, the exact model was applied in order to develop the proposed method. The approximate method requires two approximations, which only use simple algebraic functions. The first approximation is required to build an equivalent system for the simultaneous inrush currents of transformers in a distribution feeder. This equivalent system is composed by a single transformer, which is fed by an ideal voltage source connected in series with an impedance. The second approximation is required to compute the maximum inrush current of a transformer by assuming that the source impedance is not negligible. These novel approximations were tested for diverse integration time intervals. The results show that the accuracy of the developed method can be considered suitable because the average percentage error, in comparison with the exact model, is in the order of 4% for the first approximation and 5% for the second approximation. The developed method allows a straightforward calculation of the maximum rms current in a feeder due to inrush currents in downstream transformers, and the knowledge of this magnitude is useful for the proper coordination of overcurrent devices in electric power distribution systems. (C) 2016 Elsevier B.V. All rights reserved.
机译:本文展示了一种计算近似值的方法,该方法可以计算出由于下游变压器同时涌入电流而在配电馈线中产生的最大均方根电流。在本文的第一部分中,测试了一种用于精确计算配电变压器中涌入电流的方法(通过求解微分方程)。通过实验测量验证了该精确模型。随后,使用精确模型来开发所提出的方法。近似方法需要两个近似,它们仅使用简单的代数函数。对于配电馈线中的变压器的同时涌入电流,需要建立一个近似系统来建立等效系统。该等效系统由单个变压器组成,该变压器由与阻抗串联的理想电压源供电。通过假定源阻抗不可忽略,需要第二个近似值来计算变压器的最大浪涌电流。这些新颖的近似值已针对不同的积分时间间隔进行了测试。结果表明,由于与精确模型相比,平均百分比误差在第一次近似中约为4%,在第二次近似中约为5%,因此可以认为该方法的准确性是合适的。所开发的方法可以直接计算由于下游变压器中的涌入电流而引起的馈线中的最大均方根电流,并且该量级的知识对于配电系统中过电流设备的正确协调很有用。 (C)2016 Elsevier B.V.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号