Surge and energization tests and modeling on a 225 kV HVAC cable

机译:225 kV HVAC电缆的电涌和通电测试和建模

获取原文
获取原文并翻译 | 示例
       

摘要

This paper presents experimental results from surge and energization field tests carried out on a 225 kV underground XLPE cable with 64 km and 17 major sections with cross-bonding of sheaths. The surge tests applied a 2 kV surge to minor and major sections having 1080 m and 3952 m, respectively. The tests on the minor section were intended to excite different propagation modes and observe the respective cable responses. In the energization tests, the transient current and voltage at the sending end were measured, when energizing the full cable, from each end. Measured results of current show the impact of transformers in the network and the reactive compensator. The energization tests were simulated in EMTP using detailed and simplified cable models, corresponding to using a separate model for each cable minor section or a homogeneous equivalent for the whole cable length. Computed results show that using the simplified model does not reduce the accuracy of simulations of core voltages and currents, because the simulated test concerned only core conductor quantities. (C) 2018 Elsevier B.V. All rights reserved.
机译:本文介绍了在225 kV地下XLPE电缆上进行的电涌和通电现场试验的实验结果,该电缆长度为64 km,主要段为17个,交叉护套。浪涌测试对分别具有1080 m和3952 m的较小和主要部分施加了2 kV的浪涌。较小部分的测试旨在激发不同的传播模式并观察相应的电缆响应。在通电测试中,当给整根电缆通电时,从两端测量发送端的瞬态电流和电压。电流的测量结果显示了网络中的变压器和无功补偿器的影响。通电测试是在EMTP中使用详细和简化的电缆模型进行仿真的,对应于对每个电缆小段使用单独的模型,或者对整个电缆长度使用同等的等效模型。计算结果表明,使用简化模型不会降低铁芯电压和电流仿真的准确性,因为仿真测试仅涉及铁芯导体数量。 (C)2018 Elsevier B.V.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号