Fault Ride-Through Capability Improvement of Grid Connected PV System Using Dynamic Voltage Restorer

机译:使用动态电压恢复器的电网连接光伏系统的故障乘转

获取原文
获取原文并翻译 | 示例

摘要

When a fault occurs at a grid-connected photovoltaic (PV) system, the grid voltage drops significantly, and this causes a spike in the DC link voltage. The high DC voltage, in turn, causes faults in the Power-Electronics inverters and choppers. In addition, PV plants form a significant portion of modern power systems and disconnecting them during faults (as conventional) is no longer an option. This work proposes the dynamic voltage restorer (DVR) to improve the fault ride-through (FRT) capability of PV systems under a three-phase-to-ground fault. In order to evaluate the effectiveness of the proposed DVR method, its performance is compared with that of the series dynamic braking resistor (SDBR). The comparison is made in terms of performance and control complexity. Simulation results show that the DVR can improve the FRT capability seamlessly. Also, despite its higher cost and controller complexity, the proposed DVR outperforms the SDBR in all aspects.
机译:当在网格连接的光伏(PV)系统时发生故障时,电网电压显着降低,这导致直流链路电压中的尖峰。 反过来,高直流电压导致电力 - 电子逆变器和切换器中的故障。 此外,PV工厂形成了一部分现代电力系统,并在故障期间断开它们(常规)不再是一种选择。 这项工作提出了动态电压恢复器(DVR),以提高PV系统在三相到地上的故障下的故障骑行(FRT)能力。 为了评估所提出的DVR方法的有效性,将其性能与串联动态制动电阻(SDBR)进行比较。 比较是在性能和控制复杂性方面进行的。 仿真结果表明,DVR可以无缝地改善FRT功能。 此外,尽管成本较高,但是控制器复杂性较高,所提出的DVR在所有方面都赢得了SDBR。