A defect such as a free metallic particle or stress-raising edge on an electrode could lead to breakdown in a gas insulated substation (GIS), but may be detected by the partial discharges it generates. Of the various detection means available, most success has been achieved with either acoustic transducers to detect sound waves from the discharge, or electrical couplers to pick up the ultra-high-frequency (UHF) signals generated inside the GIS chambers. All new GIS in the UK are fitted with internal couplers for UHF monitoring, and two examples of continuous monitoring schemes on 400 kV GIS at nuclear power stations are described. Further developments, which are already well advanced, include specifying and measuring the coupler characteristics, making use of expert systems to interpret the UHF discharge data, and extending the monitoring system to include the performance of circuit breakers and other equipment.
机译:诸如游离金属颗粒或电极上的应力升高边缘之类的缺陷可能导致气体绝缘变电站(GIS)击穿,但可以通过其产生的局部放电来检测。在可用的各种检测手段中,用声换能器检测放电声波或用电耦合器拾取GIS腔室内产生的超高频(UHF)信号已取得了最大的成功。英国所有新的GIS都装有用于UHF监测的内部耦合器,并描述了两个在核电站进行的400 kV GIS连续监测方案的示例。已经取得了很大进展的进一步发展包括指定和测量耦合器特性,利用专家系统解释UHF放电数据以及将监视系统扩展到包括断路器和其他设备的性能。