Since the majority of vacuum circuit breakers in use are of the single-break variety, there have been few studies of double-break vacuum circuit breakers. This report describes our investigations of the interruption characteristics of the double-break vacuum circuit breaker. In this investigation, the post arc current and recovery voltage distribution ratio were measured in order to clarify the relationship between them. The results show that a bias of the voltage distribution ratio occurs when the post arc current value becomes imbalanced. In addition, the measurements of the post arc current for circuit breakers with spiral contacts are very scattered as compared with those with axial magnetic field contacts. Normally, the double-break vacuum circuit breaker consists of two contacts of the same type. However, when two spiral contacts are used, the scattering of post arc current causes a current imbalance. As a result, a bias of the voltage distribution ratio may occur. It appears to be preferable to use double-break vacuum circuit breakers with axial magnetic field contacts.
机译:由于使用中的大多数真空断路器属于单断路器类型,因此很少有关于双断路器真空断路器的研究。该报告描述了我们对双断路真空断路器的断路特性的调查。在这项研究中,测量了电弧后电流和恢复电压的分配比率,以阐明它们之间的关系。结果表明,当电弧后电流值变得不平衡时,会出现电压分配比的偏差。另外,与具有轴向磁场触点的断路器相比,具有螺旋触点的断路器的电弧后电流的测量值非常分散。通常,双断路真空断路器由两个相同类型的触点组成。但是,当使用两个螺旋触点时,电弧后电流的散射会导致电流不平衡。结果,可能出现电压分配比的偏差。似乎最好使用带有轴向磁场触点的双断路器真空断路器。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号