首页> 外文期刊>Dielectrics and Electrical Insulation, IEEE Transactions on >Improving the accuracy of SF6 leakage detection for high voltage switchgear
【24h】

Improving the accuracy of SF6 leakage detection for high voltage switchgear

机译:提高高压开关柜SF6泄漏检测的准确性

获取原文
获取原文并翻译 | 示例
           

摘要

Even though average leakage rates of SF6 in high voltage equipment are very low, there is no guarantee for a 100% leakage-free system, especially when considering the generally long lifespan of high-voltage equipment. Taking in view the rather strict maximum allowed leakage rate of SF6 per year, regulated by international standards, these facilities should be equipped with suitable monitoring devices. However, accurate detection of low rates of gas leakage is not an easy task. This paper sheds light on the challenges of leakage detection by thorough analysis of physical aspects. Furthermore, it proposes two methods for high-fidelity leakage monitoring and detection with special emphasis on their suitability for use in substations. Application of these methods in the laboratory environment revealed an accuracy of detection levels of 0.3% per year. This is a substantial improvement from the present monitoring systems that show fluctuation levels of the indicator to be as high as up to several percent, which is clearly above the acceptable level.
机译:即使高压设备中SF6的平均泄漏率非常低,也无法保证100%无泄漏的系统,尤其是考虑到高压设备的使用寿命通常较长时。考虑到国际标准规定的每年相当严格的SF6最大允许泄漏率,这些设施应配备合适的监测装置。但是,准确检测低漏气率并非易事。通过对物理方面的全面分析,本文揭示了泄漏检测的挑战。此外,它提出了两种用于高保真泄漏监测和检测的方法,其中特别强调了它们在变电站中的适用性。这些方法在实验室环境中的应用显示出每年0.3%的检测精度。与目前的监控系统相比,这是一个重大的改进,目前的监控系统显示指标的波动水平高达百分之几,明显高于可接受水平。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号