To pre-discover the insulating defects and avoid possible insulation failures, DC withstand voltage test with partial discharge (PD) measurements are routinely conducted before the operation of a convertor transformer. However, a “downward trend” of PDs under DC voltage studied in this paper indicates the limitation of the current test. According to the study, under DC voltage both PD magnitude and PD repetition rate decrease with voltage applying time. At Updiv=29 kV, the average charge is 105 pC in the first 10 min and 33 pC in the last 10 min. Whereas for 3Updiv=87 kV, the value are 2700 pC and 1561 pC separately. On the other hand, at Updiv, PD numbers decrease from 12 times in the first 10 min to 5 times in the last 10 min. At 3Updiv, the numbers are 102 times and 83 times. When PD magnitude is higher than 1400 pC, a whitish area appears at the surface of the pressboard, accompanied by the decrease of DC withstand voltage after 2 hours' PD exposure. The results raise the question that the current test measures PDs over 2000 pC in the last 30 minutes but may introduce PDs of higher magnitude at the early stage, which will damage the dielectrics. Based on further analysis, an improved test procedure is suggested.
机译:为了预先发现绝缘缺陷并避免可能的绝缘故障,在转换变压器运行之前,通常会进行带有局部放电(PD)测量的直流耐压测试。但是,本文研究的PD在直流电压下的“下降趋势”表明了电流测试的局限性。根据研究,在直流电压下,PD幅值和PD重复率均会随电压施加时间而降低。在Updiv = 29 kV时,前10分钟的平均电荷为105 pC,后10分钟的平均电荷为33 pC。而对于3Updiv = 87 kV,该值分别为2700 pC和1561 pC。另一方面,在Updiv,PD值从前10分钟的12倍减少到后10分钟的5倍。在3Updiv,这个数字是102倍和83倍。当PD值高于1400 pC时,压板表面会出现发白的区域,并且暴露2小时后,DC耐压会降低。结果提出了一个问题,即当前的测试在最近30分钟内测量的PD超过2000 pC,但可能会在早期引入更高幅度的PD,这会损坏电介质。在进一步分析的基础上,提出了一种改进的测试程序。

著录项

  • 来源
  • 作者单位

    State Key Laboratory of Electrical Insulation and Power Equipment, School of Electrical Engineering, Xi'an Jiaotong University, Xi'an, 710049, China;

    State Key Laboratory of Electrical Insulation and Power Equipment, School of Electrical Engineering, Xi'an Jiaotong University, Xi'an, 710049, China;

    State Key Laboratory of Electrical Insulation and Power Equipment, School of Electrical Engineering, Xi'an Jiaotong University, Xi'an, 710049, China;

    State Key Laboratory of Electrical Insulation and Power Equipment, School of Electrical Engineering, Xi'an Jiaotong University, Xi'an, 710049, China;

    Electric Power Research Institute, Yunnan Power Grid Co., Ltd. Kunming, 650217, China;

    Electric Power Research Institute, Yunnan Power Grid Co., Ltd. Kunming, 650217, China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Partial discharges; Partial discharge measurement; Converters; Discharges (electric); Electrodes; Surface discharges;

    机译:局部放电;局部放电测量;转换器;放电(电);电极;表面放电;