The design of cooling tower`s filler unit, consisting of inclined-corrugated contact elements, and made of polymer material, is developed and described in this research paper. The experimental studies were conducted to determine the efficiency of cooling the circulating water in the proposed cooling tower. The authors obtained the results of evaluating the heat-mass transfer efficiency coefficient of cooling tower, when changing the mass flow rates of liquid and gas phases. The research results showed that the highest efficiency of cooling the circulating water is observed at relatively low irrigation densities equal to 15-25 m~(3)/(m~(2)·h), while the heat-mass transfer efficiency of cooling tower achieves 72%.The use of non-metal materials as the main elements of cooling tower allows to abandon the use of chemical reagents against bacteria and microorganisms in favor of circulating water ozonation method.
机译:通过倾斜波纹接触元件和由聚合物材料制成的冷却塔填料单元的设计是在本研究论文中进行的和由聚合物材料制成的。进行实验研究以确定在所提出的冷却塔中冷却循环水的效率。当改变液相和气相的质量流速时,作者获得了评估冷却塔的热传质效率系数的结果。研究结果表明,在相对较低的灌溉密度下观察到循环水的最高效率,等于15-25m〜(3)/(m〜(2)·h),而冷却的热量传递效率塔达到72%。使用非金属材料作为冷却塔的主要元素允许放弃使用化学试剂对细菌和微生物,以支持循环水臭氧化方法。