Due to the high number of cases in which fire accidents were initiated from pipe insulation materials installed in small compartments, flame-retardant products should be used in building construction. Typically, standardised rectangular type specimens are used to evaluate the reaction-to-fire performance of pipe insulation without considering the actual installation conditions. In this study, polyethylene (PE) foam pipe insulation materials were tested, taking construction methods into account, according to the NFPA 274 standard. The experimental results showed that the fire growth rate varied from ultrafast to slow, depending on the installation conditions, and that the time to reach the peak heat release rate varied significantly. In particular, the addition of a galvanised steel casing lowered the fire risk even if the same PE foam material was used. Therefore, to improve fire safety in small compartments, such as concealed or interstitial spaces that do not have active fire protection systems, using galvanised steel casings is an alternative method for building construction.
机译:由于从安装在小隔间安装在小隔间的管道绝缘材料的情况下,阻燃产品应在建筑施工中使用。通常,标准化的矩形样本标本用于评估管道绝缘的反应性能,而不考虑实际的安装条件。在该研究中,测试了聚乙烯(PE)泡沫管绝缘材料,考虑到施工方法,根据NFPA 274标准。实验结果表明,取决于安装条件,消防速度从超速度变化,速度变化,并且达到峰值热释放速率的时间显着变化。特别地,即使使用相同的PE泡沫材料,也可以加入镀锌钢壳体降低了火灾风险。因此,为了改善小隔间中的消防安全,例如没有有源防火系统的隐藏或间隙空间,使用镀锌钢壳是建筑结构的替代方法。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号