首页> 外文期刊>日本建築学会大会学術講演梗概集 >Development of radiant floor cooling system using phase change material under hot and humid climates
【24h】

Development of radiant floor cooling system using phase change material under hot and humid climates

机译:在热潮湿气候下使用相变材料的辐射地板冷却系统的开发

获取原文
获取原文并翻译 | 示例

摘要

In this paper, a new radiant floor cooling system using phasechange materials was proposed, and the results of preliminarymeasurement using experimental units was presented. The keyfindings are summarized as follows:(1) The cooling effect of the proposed floor radiant coolingsystem was observed. The maximum reduction of surfacetemperature of floor was up to 1.6°C. On the other hand, thenocturnal surface temperature was increased byapproximately 1.0°C.(2) There was a difference of cooling effect between north areaand south area. The maximum difference was approximately0.6°C. This was probably due to the location of exhaust fans.(3) PCMs can store approximately 450-453 kJ/m2 of heat duringnight-time by this system. 56-59 % of the amount of coolstorage were found to contribute to reduce the floortemperature during daytime of the following day.
机译:本文采用了一种新的辐射地板冷却系统,使用相位提出了改变材料,初步的结果提出了使用实验单元的测量。钥匙调查结果总结如下:(1)建议地辐射冷却的冷却效果观察到系统。表面的最大减少地板的温度高达1.6°C。另一方面,夜间表面温度增加大约1.0°C。(2)北方地区之间的冷却效果存在差异和南部地区。最大差异约为0.6°C。这可能是由于排气扇的位置。(3)PCMS可以在此期间存储大约450-453 kJ / m2的热量这个系统的夜间。 56-59%的凉爽发现存储有助于减少地板第二天白天的温度。