Investigations on the safe stroke of mechanical HVDC vacuum circuit breaker

机译:机械HVDC真空断路器安全行程的研究

获取原文
获取原文并翻译 | 示例
           

摘要

Here, a DC vacuum arc interruption test based on the hybrid high-speed actuator and the method of commutation is carried out in the synthetic loop system. The safe stroke is one of the basic breaking parameters. The minimum safe stroke directly determines the commutation time and breaking property of the mechanical DC vacuum circuit breaker. The main circuit breaker is a high-speed vacuum switch driven by electromagnetic repulsion actuator. In order to simplify its control system, the commutation switch also adopts high-speed vacuum switch. The main current source for verification test of this DC breaker system is provided by a LC oscillator circuit with lower frequency. Simulations with some experiments were completed on breaking process of this system by PSCAD. The breaking current is 4 kA by the DC breaker system proposed here, the opening speed is about 2.417 m/s in this experimental system; From the results, the simulation and experimental waveforms are compared and analysed, and some effects on safe stroke of the DC vacuum circuit breaker is studied. The shortest arcing time is about 0.89 ms and the minimum safe stroke is about 2.15 mm under the lower voltages.
机译:这里,基于混合高速致动器的DC真空电弧中断测试和换向方法在合成回路系统中进行。安全行程是基本的断开参数之一。最小安全行程直接确定机械直流真空断路器的换向时间和断裂性。主断路器是由电磁排斥致动器驱动的高速真空开关。为了简化其控制系统,换向开关还采用高速真空开关。该直流断路器系统的验证测试的主电流源由具有较低频率的LC振荡器电路提供。通过PSCAD完成了一些实验的模拟。在此提出的DC断路器系统,断路电流为4kA,在该实验系统中开口速度约为2.417m / s;从结果,对模拟和实验波形进行了比较和分析,研究了对DC真空断路器的安全行程的一些效果。最短的电弧时间约为0.89毫秒,下电压下最小安全行程约为2.15毫米。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号