Vacuum circuit breakers (VCB) are commonly used in active mechanical direct current circuit breakers (DC CBs) to accomplish the interruption of the fault current. The post-arc current phenomenon of a VCB is related to the dielectric recovery process of the VCB. Thus, we performed experiments to investigate the influence on the post-arc current by taking the electrode separation, breaking current, and interruption of the bi-directional current with the injecting high frequency current in a fixed direction into account. To be in accordance with the practical interruption duty, the breaking current in the experiment ranges from 500?A to 20 kA. At the same time, the di/dt at current zero (CZ) varies between 200 and 1100 A/μs. The experiment results reveal that the peak value of the post-arc current in an active DC circuit breaker can reach more than 100?A with high di/dt at CZ. It is found that with a longer electrode separation, not only the residual charge increases but also the post-arc current increases. The arcing current before CZ can influence the post-arc current but the effective duration before CZ is short. This duration is the memory time and it is derived from the experiment results. The influence of the breaking current and interruption of the bi-directional current with the injecting current in a fixed direction are dependent on the relation of the current commutation time with the memory time.
机译:真空断路器(VCB)通常用于有源机械直流断路器(DC CBS),以实现故障电流的中断。 VCB的后电流电流现象与VCB的介电恢复过程有关。因此,我们通过将电极分离,断路器电流和双向电流的中断以固定的方向注入固定方向来研究对电弧电流对电弧电流对电弧电流影响的实验。符合实际中断职责,实验中的断裂电流范围为500?a至20 ka。同时,电流零(CZ)的DI / DT在200到1100A /μs之间变化。实验结果表明,有源直流断路器中电弧电流的峰值可以在CZ中具有高DI / DT的100多倍。发现,通过较长的电极分离,不仅剩余电荷增加而且电弧电流也增加。 CZ之前的电弧电流可以影响电弧电流,但CZ短的有效持续时间。此持续时间是存储时间,它来自实验结果。在固定方向上与注入电流的断裂电流和中断的影响是取决于当前换向时间与存储时间的关系。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号