首页> 外文期刊>MATEC Web of Conferences >A qualitative investigation on double-skin fa?ade fires
【24h】

A qualitative investigation on double-skin fa?ade fires

机译:对双层外墙火灾的定性研究

获取原文
       

摘要

Fire hazard of the green architectural feature double-skin façade is always a concern. A hazard scenario with a room fire adjacent to the façade was identified earlier after interviewing with fire professionals. Experimental studies on the consequence of the fire hazard due to trapping heat and mass in the façade cavity carried out before will be reported in this presentation. The rig was of height 15 m with a fire chamber placed next to it. Flashover was induced to direct hot flame and smoke out. Only part of the building was studied instead of a full height façade due to resource limitations. Air temperature next to the upper interior glass pane was confirmed to be higher than the air temperature next to the exterior pane with normal air cavity depth in double-skin façades. Flame will then be diverted to the interior glass pane, giving possibility to spread fire to the upper rooms.
机译:绿色建筑特色的双层皮肤立面着火的隐患一直是人们关注的问题。在与消防人员进行访谈后,较早发现了立面附近有室内火灾的危险场景。本演讲将报道因之前在立面腔中滞留热量和物质而引起火灾危险的实验研究。钻机高度为15 m,旁边有一个火室。闪络被引导来引导热火焰和烟雾。由于资源限制,仅对建筑物的一部分进行了研究,而不是对整个立面进行了研究。在双层玻璃幕墙中,正常内部空腔深度的情况下,上部内部玻璃窗格旁边的空气温度被证实高于外部窗格玻璃旁边的空气温度。然后,火焰将转移到内部玻璃板上,从而有可能将火势蔓延到较高的房间。