首页> 外文期刊>IFAC PapersOnLine >Hybrid State Estimation Model Based on PMU and SCADA Measurements
【24h】

Hybrid State Estimation Model Based on PMU and SCADA Measurements

机译:基于PMU和SCADA测量的混合状态估计模型。

获取原文
           

摘要

Abstract: In this paper, a new method of hybrid non-linear state estimation with PMU and SCADA measurements will be proposed. PMU measurements, the voltage and current phasors, are used for real time transmission line parameters (impedance and admittance) calculation. Transmission line parameters are input data for the conventional state estimator. Calculated parameters of the transmission lines based on the real time PMU measurements are compared with the measured impedance and admittance. The simulation results were carried out on 400 kV Croatian power system. An index of accuracy is set and used to quantify the impact of PMU measurements on power system state estimation by using proposed hybrid model. Software for the proposed hybrid model was developed and it is compatible with PMUs form different vendors. This research was made possible by implementation of 5 PMUs and restoration of wide area monitoring (WAM) system in Croatian power system. Those PMUs were implemented during the reconnection process - reintegration of the 1 st and 2 nd UCTE synchronous zone.
机译:摘要:本文提出了一种结合PMU和SCADA测量的非线性非线性状态估计的新方法。 PMU测量(电压和电流相量)用于实时传输线参数(阻抗和导纳)计算。传输线参数是常规状态估计器的输入数据。将基于实时PMU测量的传输线计算参数与测量的阻抗和导纳进行比较。仿真结果是在400 kV克罗地亚电力系统上进行的。通过使用建议的混合模型,可以设置一个精度指标,并将其用于量化PMU测量对电力系统状态估计的影响。开发了用于所提议的混合模型的软件,并且该软件与来自不同供应商的PMU兼容。通过实施5个PMU和恢复克罗地亚电力系统中的广域监视(WAM)系统,使这项研究成为可能。这些PMU是在重新连接过程中实现的-第一和第二UCTE同步区域的重新集成。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号