Effectiveness of 1-bromo-3-chloro-5,5-dimethylhydantoin against Legionella pneumophila in a cooling tower.

机译:1-溴-3-氯-5,5-二甲基乙内酰脲对冷却塔中肺炎军团菌的有效性。

获取原文
   

获取外文期刊封面封底 >>

       

摘要

Cooling towers are considered to be man-made amplifiers of Legionella spp. Thus, the proper maintenance and choice of biocides is important. The only biocidal measure that has thus far been shown to be effective in field tests is the judicious use of chlorination. Perturbation studies with 1-bromo-3-chloro-5, 5-dimethylhydantoin (Bromicide; Great Lakes Chemical Corp., West Lafayette, Ind.) (BCD) were conducted on an industrial cooling tower shown to contain Legionella pneumophila. At the concentrations recommended by the manufacturer, neither the density nor the activity of L. pneumophila was affected. At comcentrations greater than 2.0 ppm (2.0 micorgram/ml) free of residual, BCD was not effective in reducing L. pneumophila to source water concentrations, nor was it effective in reducing the 2-p-iodophenyl-3-p-nitrophenyl-5-phenyl tetrazolium chloride activity of the bacterium in situ. The data indicate that at concentrations up to 2.0 ppm, BCD is not effective in these tower studies.
机译:冷却塔被认为是军团菌属的人造放大器。因此,正确维护和选择杀生物剂很重要。迄今为止,已证明在现场测试中有效的唯一杀菌措施是明智地使用氯化法。在显示含有肺炎军团菌的工业冷却塔上进行了1-溴-3-氯5,5-二甲基乙内酰脲(杀菌剂; Great Lakes Chemical Corp.,西拉法叶,印第安纳州)(BCD)的扰动研究。在制造商建议的浓度下,嗜肺乳杆菌的密度和活性均未受影响。在浓度大于2.0 ppm(2.0微克/毫升)且无残留的情况下,BCD不能有效地降低嗜肺杆菌(L. pneumophila)产生的水源浓度,也不能有效地降低2-p-碘苯基-3-p-硝基苯基-5 -苯基四唑鎓细菌的原位活性。数据表明,浓度高达2.0 ppm时,BCD在这些塔研究中无效。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号