首页> 外文期刊>Chemotherapy: International Journal of Experimental and Clinical Chemotherapy >Effectiveness of disinfectants used in cooling towers against Legionella pneumophila.
【24h】

Effectiveness of disinfectants used in cooling towers against Legionella pneumophila.

机译:冷却塔中使用的消毒剂针对军团菌的效果。

获取原文
获取原文并翻译 | 示例

摘要

BACKGROUND: Legionella persists in man-made aquatic installations despite preventive treatments. More information about disinfectants could improve the effectiveness of treatments. This study tests the susceptibility of Legionella pneumophila serogroup (sg) 1 against 8 disinfectants used in cooling tower treatments. METHODS: We determined the minimal inhibitory concentration (MIC), minimal bactericidal concentration (MBC) and bactericidal effect of sodium hypochlorite (A), hydrogen peroxide with silver nitrate (B), didecyldimethylammonium chloride (C), benzalkonium chloride (D), tributyltetradecylphosphonium chloride (E), tetrahydroxymethylphosphonium sulfide (F), 2,2-dibromonitropropionamide (G) and chloromethylisothiazolone (H) against 28 L. pneumophila sg 1 isolates. RESULTS: MIC and MBC values were equivalent. Bacteria are less susceptible to disinfectants F, B, D and A than to H, E, C and G. All disinfectants induced a bactericidal effect. The effect rate is dose dependent for G, H, F and B; the effect is fast for the rest of disinfectants at any concentration. The bactericidal activity of disinfectants A, G and F depends on the susceptibility test used. CONCLUSIONS: All disinfectants have bactericidal activity against L. pneumophila sg 1 at concentrations used in cooling tower treatments. Results depend on the assay for some products.
机译:背景:尽管有预防性治疗,军团菌仍然存在于人造水生设施中。有关消毒剂的更多信息可以提高治疗效果。这项研究测试了军团菌嗜肺军团血清群(sg)1对冷却塔处理中使用的8种消毒剂的敏感性。方法:我们确定了次氯酸钠(A),硝酸银的过氧化氢(B),二癸基二甲基氯化铵(C),苯扎氯铵(D),三丁基十四烷基phosph的最小抑菌浓度(MIC),最小杀菌浓度(MBC)和杀菌效果。氯化物(E),四羟甲基phosph硫化物(F),2,2-二溴硝基丙酰胺(G)和氯甲基异噻唑酮(H)对抗28株肺炎嗜血杆菌sg 1分离株。结果:MIC和MBC值是等效的。细菌对F,B,D和A的敏感性低于对H,E,C和G的敏感性。所有消毒剂均具有杀菌作用。 G,H,F和B的影响率与剂量有关;对于其他浓度的消毒剂,效果很快。消毒剂A,G和F的杀菌活性取决于所使用的药敏试验。结论:在冷却塔处理中使用的浓度下,所有消毒剂均具有对肺炎链球菌sg 1的杀菌活性。结果取决于某些产品的测定。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号