Performance evaluation of the variable refrigerant flow (VRF) air-conditioning system during the heating-defrosting cyclic operation

机译:制冷/除霜循环运行期间可变制冷剂流量(VRF)空调系统的性能评估

获取原文
   

获取外文期刊封面封底 >>

       

摘要

This paper shows the performance evaluation of the variable refrigerant flow (VRF) air-conditioning system subjected to very low outdoor air temperature at which the heating-defrosting cyclic operation occurred. The objectives of the study are to know the effect of the heating-defrosting cyclic operation in the VRF air-conditioning performances and of the indoor environment thermal conditions. The one outdoor unit's and two indoor units' VRF air-conditioning system was used as a test specimen in the controlled testing chambers in which temperature and humidity were controlled. Several test cases were done covering from constant dry bulb temperature with different wet bulb temperature and for both dry bulb temperature and wet bulb temperature different. The results of the study show that the heating-defrosting cyclic operation affected the performance of the VRF air-conditioning system. It shows that the heating time changes depend on both dry bulb and wet bulb temperatures. It shows that the defrosting time is almost the same for different dry bulb and wet bulb temperatures for different heating times. The cyclic heating-defrosting operation affected the indoor air temperature by lowering the indoor air temperature during defrosting. Based on the results, necessary measures are needed to address the effect of the defrosting in the VRF air-conditioning system performance and of the indoor thermal environment conditions. The heating-defrosting cyclic operation is expected to occur when the VRF air-conditioning system is installed in an actual building in a temperate climate, and in the performance evaluation of the different VRF air-conditioning systems under these conditions, it is important to know how it affects the system's operation behavior, energy consumption and support of the indoor environment thermal conditions.
机译:本文显示了在非常低的室外空气温度(发生加热-除霜循环运行)的情况下,可变制冷剂流量(VRF)空调系统的性能评估。该研究的目的是了解加热除霜循环运行对VRF空调性能和室内环境热条件的影响。在控制温度和湿度的受控测试室内,将一个室外机和两个室内机的VRF空调系统用作测试样本。进行了几个测试案例,涵盖了恒定的干球温度和不同的湿球温度,以及干球温度和湿球温度都不同的情况。研究结果表明,加热-除霜循环运行会影响VRF空调系统的性能。它表明加热时间的变化取决于干球和湿球的温度。结果表明,在不同的加热时间下,不同的干球温度和湿球温度的除霜时间几乎相同。循环加热-除霜操作通过降低除霜期间的室内空气温度来影响室内空气温度。根据结果​​,需要采取必要的措施来解决除霜对VRF空调系统性能和室内热环境条件的影响。当将VRF空调系统安装在温带气候的实际建筑物中时,预计会发生制热-除霜循环操作,并且在这些条件下对不同VRF空调系统的性能进行评估时,重要的是要知道它如何影响系统的操作行为,能耗以及对室内环境热条件的支持。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号