首页> 外文期刊>Journal of Thermal Engineering >Thermodynamic Performance Analysis of Dedicated Mechanically Subcooled Vapour Compression Refrigeration System
【24h】

Thermodynamic Performance Analysis of Dedicated Mechanically Subcooled Vapour Compression Refrigeration System

机译:专用机械过冷蒸汽压缩制冷系统的热力学性能分析

获取原文
       

摘要

In this work, the thermodynamic analysis of dedicated mechanically subcooled vapour compression refrigeration system is presented. A software based computer program in EES has been formulated for computation of the performance results. The effect of varation of degree of subcooling (5-30oC), evaporator temperature (-20 to 10oC) and condenser temperature (30-50oC) has been investigated for energetic and exergetic performance of the system. The analysis of the system has been carried out using zero ODP and very low GWP (1 to 4) refrigerants viz.HFO-R1234ze and R1234yf to compare the performance of HFC-R134a. The results depicts that the COP and exergetic efficiency of dedicated subcooled VCR cycle are better than that of simple VCR cycle. Refrigerant R1234ze performs better than R1234yf and comparable to R134a.
机译:在这项工作中,介绍了专用机械过冷蒸气压缩制冷系统的热力学分析。已经制定了EES中基于软件的计算机程序,用于计算性能结果。研究了过冷度(5-30oC),蒸发器温度(-20至10oC)和冷凝器温度(30-50oC)的变化对系统的能量和能量性能的影响。使用零ODP和非常低的GWP(1-4)制冷剂即HFO-R1234ze和R1234yf进行了系统分析,以比较HFC-R134a的性能。结果表明,专用过冷VCR循环的COP和能量效率均优于简单VCR循环。 R1234ze制冷剂的性能优于R1234yf,与R134a相当。