首页> 外文期刊>Journal of Engineering Research >Experimental verification of a new positive feedback islanding detection method for grid-connected inverter
【24h】

Experimental verification of a new positive feedback islanding detection method for grid-connected inverter

机译:并网逆变器正反馈孤岛检测新方法的实验验证

获取原文
           

摘要

Islanding detection is one of the most importantissues for grid-connected inverter applications. A new positive-feedbackanti-islanding method is presented in this paper. It utilizes the negativesequence voltage component as a positive feedback variable, and no additionalnegative sequence disturbance is needed at all. After islanding, the positivefeedback loop will force the negative sequence voltage component away from thenominal value. A new negative sequence estimation algorithm is alsopresented for the successful islanding detection. Finally, the experimental testsare carried out to verify the effectiveness of the proposed method.
机译:孤岛检测是并网逆变器应用中最重要的问题之一。本文提出了一种新的正反馈反孤岛方法。它利用负序电压分量作为正反馈变量,根本不需要其他负序干扰。孤岛后,正反馈环路将迫使负序电压分量偏离标称值。提出了一种新的负序列估计算法,用于成功的孤岛检测。最后,通过实验测试验证了所提方法的有效性。