首页> 外文期刊>Journal of Electrical Engineering >Disturbances in the European Nuclear Power Plant Safety Related Electrical Systems
【24h】

Disturbances in the European Nuclear Power Plant Safety Related Electrical Systems

机译:欧洲核电厂安全相关电气系统的故障

获取原文
           

摘要

Disturbances in the European Nuclear Power Plant Safety Related Electrical Systems This work is part of the European Clearinghouse on Nuclear Power Plant Operational Experience Feedback (NPP-OEF) activity carried out at the Joint Research Centre/Institute for Energy (JRC/IE) with the participation of ten EU Regulatory Authorities. It investigates the Forsmark-1 event of July 2006, as well as about 120 disturbances in the plant electrical systems that were reported to the Incident Reporting System (IRS) and US Licensee Event Reports (LER) in the period 1985-2008. The aim of the work was to provide important insights from the Forsmark event of July 2006 and illustrate some vulnerabilities of the plant electrical system to over voltage transients. It identified electrical equipment involved, failure modes, contributing factors, actual and potential consequences, and corrective actions. Initiating factors and associated root causes were also analysed. The analysis of International Operation Experience Feedback revealed number of events that involved disturbances in the plant electrical systems, and which may have features in common with the Forsmark-1 event. It underlines the importance of sharing lessons learned from design modifications made at another unit of similar design that if known, it could have identified susceptibility of emergency diesel generators to common mode failure before the event occurred. This paper also summarizes international projects that were initiated by Forsmark event, as well as important lessons that still can be learned from Forsmark event. This paper presents actions taken at nuclear power plants and regulatory authorities in different countries to prevent similar event to occur.
机译:欧洲核电厂安全相关电气系统的故障这项工作是欧洲核电厂运行经验反馈信息交换所(NPP-OEF)活动的一部分,该活动是在联合研究中心/能源研究所(JRC / IE)的协助下进行的。十个欧盟监管机构的参与。它调查了2006年7月的Forsmark-1事件,以及在1985-2008年期间向事件报告系统(IRS)和美国被许可方事件报告(LER)报告的工厂电气系统中的大约120种干扰。这项工作的目的是从2006年7月的Forsmark事件中提供重要的见解,并举例说明工厂电气系统对过电压瞬变的一些脆弱性。它确定了所涉及的电气设备,故障模式,影响因素,实际和潜在后果以及纠正措施。还分析了引发因素和相关的根本原因。对《国际运行经验反馈》的分析显示,许多事件涉及工厂电气系统中的干扰,并且可能具有与Forsmark-1事件相同的特征。它强调了分享从在类似设计的另一个单元进行的设计修改中汲取的经验教训的重要性,该经验教训是,如果知道的话,它可以在事件发生之前确定应急柴油发电机对共模故障的敏感性。本文还总结了由Forsmark事件发起的国际项目,以及仍可以从Forsmark事件中学到的重要课程。本文介绍了在不同国家的核电厂和监管机构采取的措施,以防止类似事件的发生。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号