首页> 外文期刊>Serbian Journal of Electrical Engineering >Acoustic emission partial discharge detection technique applied to fault diagnosis: Case studies of generator transformers
【24h】

Acoustic emission partial discharge detection technique applied to fault diagnosis: Case studies of generator transformers

机译:声发射局部放电检测技术在故障诊断中的应用:发电机变压器案例研究

获取原文
           

摘要

In power transformers, locating the partial discharge (PD) source is as important as identifying it. Acoustic Emission (AE) sensing offers a good solution for both PD detection and PD source location identification. In this paper the principle of the AE technique, along with in-situ findings of the online acoustic emission signals captured from partial discharges on a number of Generator Transformers (GT), is discussed. Of the two cases discussed, the first deals with Acoustic Emission Partial Discharge (AEPD) tests on two identical transformers, and the second deals with the AEPD measurement of a transformer carried out on different occasions (years). These transformers are from a hydropower station and a thermal power station in India. Tests conducted in identical transformers give the provision for comparing AE signal amplitudes from the two transformers. These case studies also help in comprehending the efficacy of integrating Dissolved Gas is (DGA) data with AEPD test results in detecting and locating the PD source.
机译:在电力变压器中,定位局部放电(PD)源与识别局部放电一样重要。声发射(AE)感测为PD检测和PD源位置识别提供了一个很好的解决方案。本文讨论了声发射技术的原理,以及从一些发电机变压器(GT)上的局部放电捕获的在线声发射信号的现场发现。在讨论的两个案例中,第一个涉及在两个相同的变压器上的声发射局部放电(AEPD)测试,第二个涉及在不同场合(年份)进行的变压器的AEPD测量。这些变压器来自印度的水力发电厂和火力发电厂。在相同的变压器中进行的测试可以比较两个变压器的AE信号幅度。这些案例研究还有助于理解将溶解气体(DGA)数据与AEPD测试结果进行集成以检测和定位PD源的功效。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号