首页> 外文期刊>Research journal of applied science, engineering and technology >Improving Transient Recovery voltage of circuit breaker using Fault Current Limiter
【24h】

Improving Transient Recovery voltage of circuit breaker using Fault Current Limiter

机译:使用故障电流限制器提高断路器的瞬态恢复电压

获取原文
           

摘要

This study investigates influence of Fault Current Limiter (FCL) on short-circuits current level of substation bus bar splitter circuit breaker and its TRV. An approach for TRV evaluation is developed and applied for proposed power system as shown in this study. FCL circuit is connected to the power system in order to limit TRV. The limiter circuit consists of two equal windings which are turned around unique magnetic core. One of the windings is connected in series with the power system network and the other is connected to the network via series capacitor and power electronic switches. During normal operating condition, both tyristors are in on state and current of the primary and secondary windings are equal. This causes zero impedance of the limiter. During fault, faults current cause the power electronic switch to turn off which increases the limiter impedance. By increasing the limiter impedance, amplitude of TRV decreases substantially. The novel method presented in this study is a cheap and successful scheme.
机译:本研究调查了故障电流限制器(FCL)对变电站母线分离器断路器及其TRV短路电流水平的影响。开发了TRV评估方法,并将其应用于建议的电力系统,如本研究所示。 FCL电路连接到电力系统以限制TRV。限幅器电路由两个相等的绕组组成,它们绕独特的磁芯转动。绕组之一与电力系统网络串联连接,另一绕组通过串联电容器和电力电子开关连接至网络。在正常工作状态下,两个晶闸管均处于导通状态,并且初级绕组和次级绕组的电流相等。这导致限制器的阻抗为零。在故障期间,故障电流会导致电力电子开关断开,从而增加限制器阻抗。通过增加限制器阻抗,TRV的幅度会大大降低。在这项研究中提出的新方法是一种便宜而成功的方案。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号